A laser welding chiller keeps the laser source and optical components of a fiber laser welder at a stable temperature. Much of the source power is released as heat; if it is not removed, power drops, beam quality suffers and the unit goes into protection.
What is cooled?
- Laser source: diodes and fiber modules work in a narrow temperature band.
- Welding head and optics: the collimator and protective glass can shift focus as they heat up.
- On robotic systems, cables and torch may need extra cooling.
How is capacity determined?
The best source is the laser maker's heat load and flow data. As an estimate, output power and efficiency are considered together; the heat released is often more than the output power. Include the highest summer ambient, as air-cooled chiller capacity falls in hot weather. Dual-circuit chillers are common because the circuits need different temperatures.
Water quality and conductivity
Laser circuits usually use pure or deionised water; mains water narrows channels and raises conductivity. Renew water at intervals, check filters and use only manufacturer-approved antifreeze where freezing is possible.
Beware of condensation
Setting the water too cold causes condensation on optics in humid weather, which can permanently damage the source. Keep water above the room dew point.
Frequently asked questions
Are laser cutting and welding chillers the same?
The principle is the same; capacity and number of circuits depend on the machine.
Does the laser stop if the chiller alarms?
Most systems have a signal link; on a flow or temperature alarm the laser protects itself.