Monday–Saturday 08:30–18:30 · 24/7 technical support

Chiller Pump Selection: Flow and Pressure Calculation

Chiller Pump Selection: Flow and Pressure Calculation

Chiller pump selection determines whether the system can deliver enough water where it is needed. Even a correctly sized chiller cannot cool the machines if the pump is inadequate.

How is flow calculated?

Required flow depends on cooling load and the water temperature difference; for the same load, a smaller difference needs more flow. Targeting 3 °C instead of 5 °C on the process side increases flow by about 65%, so set the target difference first.

Pressure drop

The pump must overcome losses in piping, valves, filters, exchangers, the chiller evaporator and machine channels; calculate along the longest, most resistant line. Machines with narrow mould channels can have large losses.

Primary-secondary circuit

In large systems a primary pump runs between chiller and tank and a secondary pump between tank and machines, so the chiller runs at constant flow while the process side gets variable flow.

Redundancy and control

For critical production at least one standby pump (N+1) is recommended. A frequency inverter adjusts speed to demand and saves energy; fit a strainer at the inlet and a check valve and gauge at the outlet.

Frequently asked questions

Is an oversized pump a problem?

Excess flow causes noise, pipe wear and wasted energy; use the right pump or speed control rather than throttling.

Is the chiller's built-in pump enough?

For short simple lines it may be; long lines and multi-machine systems need a separate pump set.

Tell us about your project. Send your product, quantities and location via WhatsApp or e-mail; our engineers will calculate the load and recommend the right system in writing.

Work with us

Let's choose the right system for your process together

Send us your machine data or a photo of your plant; our engineers will calculate the heat load and prepare your written quotation within 24 hours.